PE-11N(with control functions pH/ORP Indication adjustment meter)

Advantages

・It enables the current settings to be made at the time of an error or calibration, thus taking account of safety.

・The JIS method or USA method can be chosen as the automatic calibration method.

・ON/OFF control, time division proportional control, or twin timer control can be chosen.

・The DC output can be scaled.

・It has drip-proof construction that can also be used outdoors (IP54 or equivalent); it is equipped with a sunshade cover.

Applications

・pH neutralization or oxidation/reduction treatment of drainage in the chemical industry, etc.

・Incorporation of the apparatus of each process.

・pH measurement and control in hydroponic culture, etc.

・pH measurement and control of drainage from cleaning.

・pH measurement and control for drainage from experiments, etc.

Specifications

Name PH(ORP) indication and adjustment meter
Type PE-11N
Indication LCD(with backlight)
Range of measurement pH:0.00 - 14.00 ORP:-999 - +999mV Temperature:0 - 100℃
Resolution pH:0.01pH  ORP:1mV 
Temperature compensation pH automatic temperature compensation Temperature compensation range: 0 - 60℃
Temperature compensation element 6.8kΩ・500Ω・Pt1000Ω
Calibration Automatic calibration With automatic calibration solution judgment functions pH6.86 and either pH4.01, 9.18, or 1.68 (JIS) pH7.00 and either 4.00 or 10.00 (USA)
Manual calibration pH6.86, 7.00 and solutions that differ from them by 2pH or more
Control output Control: 2 points No voltage contact output Maximum resistance load capacity: AC250V3A Zone alarm: 1 point No voltage contact output maximum load capacity: AC250V3A
Control method ON/OFF control, time division proportional control, twin timer control, zone alarm, ON/OFF relay output
Control input Output: P1, P2 only External voltage-applied signal: 1 point (EXT)AC100 - 240V External contact: 3 points (LC1, 2, 3) no voltage contact
Transmission output DC4 - 20mA (maximum load resistance: 500Ω) *Error current settings can be made.
Power supply Any voltage between AC100V and 240V
Power consumption 10VA (at no load)
Protective construction Drip-proof construction: IP54 or equivalent (when using sunshade cover)
Dimensions 138(W)×138(H)×175(D) mm
Weight About 2kg
Standard accessories Sunshade cover