Hello, Welcome !
Products
Contact Us
Products
The conductivity of the water circulating in the cooling tower is measured,and in case of excessive concentration,
the power-driven valve or solenoid valve for the replenishing water is opened or closed.
・The built-in timer enables up to 2 chemical injection pumps to be operated individually.
・The large LCD with backlight indicates the measured value of conductivity, alarm point,alarm direction, and current value.
・The settings for transmission current at the time of an error or calibration can be made arbitrarily,and safety is taken into account.
・The temperature gradient value for the conductivity of the solution being measured can also be set.
・Equipped with clock functions, settings for the pump operation start time, etc. can be made.
・By means of the range changeover (manual), measurement from low concentration to high concentration can be made.
・Adjustments of the cell constant, ZERO point, and SPAN point can be made.
・The current output corresponding to the range can be obtained.
・The meter has 2 ranges of conductivity measurement: 2000μS/cm and 20.00mS/cm,and a switching between /cm and /m can also be made.
・As for the electrode, the alternating current 5-electrode method is employed that is resistant to dirt and involves little measurement error.
・Titanium is used for the detection electrode, and PVC is used as the body material,thus having excellent corrosion resistance.
・The power supply is designed to work at any voltage between AC100 and 240V.
・A sunshade cover is included as the standard accessory, and the waterproof construction grade when the sunshade cover is fitted is IP54 or equivalent that allows the meter to be used outdoors.
・Measurement of the circulating water in a cooling tower and control of replenishing water.
・Control of replenishing water for various types of chemical solutions.
Name | Cooling tower water quality controller |
Type | CEB-51 |
Method of measurement | Alternating current 5-electrode method |
Range of measurement | Conductivity range 0- 20.00mS/cm, 0 - 2000μS/cm Manual switching /cm, /m Switchable Conversion at the reference temperature 25℃ |
Temperature compensation | Temperature compensation range: 0 - 50℃ Temperature accuracy: ±1℃ Temperature device Pt1000Ω Temperature compensation factor Automatic: 2%/℃ Manual 0.5 - 5%/℃ |
Resolution | EC:0.01mS/cm、1μS/cm |
Transmission output | DC4 - 20mA(maximum load: 500Ω) |
External input | No voltage contact: 1 point Voltage-applied contact: 1 point |
Control method | ON/OFF control |
Setting method | Power-driven valve, solenoid valve side ・Conductivity interlock(ON/OFF control, DIFF) ・24Hr timer interlock ON time/OFF time, number of times(within 24 hours) ・External input interlock Above to be chosen Chemical injection pump side ・24Hr timer interlock ON time/OFF time, number of times(within 24 hours) ・External input interlock Above to be chosen |
Control output | For power-driven valve, solenoid valve Voltage-applied output(dependent on power supply voltage) 1 point To be controlled by EC value For chemical injection pump Voltage-applied output(dependent on power supply voltage)2 points Time and number of times control |
Power supply | AC100~240V |
Operating environment | 0 - 40℃ 85%RH or less |
Outer dimensions | 138(W)×138(H)×175(D) mm |
Weight | About 2kg |
Standard accessory | Sunshade cover |
Optional item | FCS-75N |
Name | EC electrode |
Type | FCS-75N |
Cell constant | 1.0(at standard) |
Material | Detection electrode:Ti Body:PVC |
Lead length | 10m |
Contact Us
Address:Room 5005, Zone A, Youkou Park, No. 377 Chengpu Road, Shanghai|Tel:021-62317631
Contact:Mr.Liu 15900567501|E-mail:liuqiang@sh-cemco.com|Fax:021-62309736
沪公网安备 31010602001723号
Website Navigation